This site uses javascript, some functionality and content is not working if javascript is disabled

Conlit Ductrock (Fire protection board for H&V ducts)

Product Description

Conlit Ductrock is a non-combustible stone wool board faced on one side with fibreglass reinforced aluminium foil. The board contains a special granulate which releases its crystallised water in the event of fire. Conlit Ductrock is supplied in a standard thickness of 60 mm. The weight of the board depends on the added granulate.

Applications

Conlit Ductrock has been specifically developed for the fire resistant cladding of metal vertical and horizontal right-angled ventilation ducts. Depending on the product used, it is fire resistant for 60, 90 or 120 minutes.

Advantages

• Optimal fire safety, combined with acoustic and thermal insulation
• Space saving - one layer solution
• No additional reinforcement for flanges and suspensions required
• For horizontal and vertical ducts
• For fire in- and outside the ducts
• For both solid and plasterboard constructions
• Easy to handle, simple to cut to size
• Fast and easy to install using welded pins and / or parker screws
• Sturdy and safe: Tested in accordance with the European standard: EN 1366-1:1999

Thermal conductivity

PerformanceTemperatureValueUnit of measureStandard
t°m (°C)100.04λ (W/mK)EN 13162
t°m (°F)500.278λ (BTU.in/ft².h.°F)EN 13162

 

Technical properties and standards
PropertyPerformanceStandard
Reaction to fire A1EN 13501-1
  A2DIN 4102-1
Fire protectionFire resistant from 60 to 120 minutes in accordance with EN 1366-1:1999 “Fire resistance tests for service installation - Part 1: Ducts”. Certificate available upon request.
Water vapour resistance of aluminium foilSd   ≥ 350 m  EN 12086

Dimensions

Thickness mmLength mmWidth mmM2 pr. 40ft HC Packaging m2/palletPackaging
601500120032436Packed on wooden pallets